Connectable data cable protection, 2x2-pole, direct earthing

  • 5-year warranty  
  • Measuring, controlling and regulating systems  
  • Communautés Européennes, EC declaration of conformity according to EC directives  
  • Transition from LPZ 0 to LPZ 2  
  • Installation electrotechnical expertise

Connectable data cable protection, type 1+2/D1+C2 for use in measurement and control technology

• Protection device for multi-wire systems
• Direct shield earthing
• Frequency range up to 100 MHz
• Earthing via DIN rail or connection cable
• Installation width from 12.5 mm
• High system availability – no signal interruption without protection module

Application: Universal lightning and surge protection for MCR data transmission devices.

TypesMax.
contin-
uous
voltage
AC
Max.
contin-
uous
voltage
DC
Num-
ber
of
poles
VersionConnec-
tion
system
Item no.QuantitySSU
4.2 V 6 V 4 2x2-pole Terminal 5080317
 
1 piece
Connectable data cable protection, 2x2-pole, direct earthing, 5 V

Connectable data cable protection, 2x2-pole, direct earthing, 5 V

Item no. 5080317

Technical data

SPD to EN 61643-11 Type 1+2
SPD to IEC 61643-11 Class I+II
Category Type 1+2 / D1+C2
SPD to IEC 61643-21 Class I+II / D1+C2
Connection cross-section, flexible 0.14 - 1.5 mm²
Connection cross-section, multi-wire 0.14 - 2.5 mm²
Connection cross-section, rigid 0.14 - 2.5 mm²
Version 2x2-pole
Number of poles 4
Insertion loss ≤3 dB
Earthing via: Connection cable / DIN rail
Total discharge current (8/20) 20 kA
Total discharge current (10/350) 2,5 kA
Frequency range 0 - 100 MHz
Cut-off frequency 100 MHz
Maximum continuous voltage AC 4.2 V
Maximum continuous voltage DC 6 V
Impulse discharge current (10/350) 2.5 kA
Nominal discharge current (8/20 µs) 10 kA
Capacity (wire-wire) ≤30 pF
Capacity (wire-earth) ≤30 pF
Series resistance 1,2 ± 5% ohm
Lightning protection zone LPZ 0→2
Total impulse durability into C2 (8/20) 20 kA
Nominal load current AC 0.425 A
Nominal load current DC 0.6 A
Mounting of input / output Screw terminals
Installation type DIN rail 35 mm
Testing standard IEC 61643-21
Shielding connection available Yes
Shield connection Direct
Protection rating IP20
Protection level wire-wire 100 V
Protection level wire-earth 850 V
Series resistance per wire 1,2 Ω ± 5%
Signalling on device None
Connection system Terminal
Impulse durability wire-wire 10 kV / 5 kA
Impulse durability wire-earth 10 kV / 5 kA
Temperature range -40 - +80 °C

Dimensions

Length 76 mm
Width 13 mm
Height 95 mm
12 V 16 V 4 2x2-pole Terminal 5080319
 
1 piece
Connectable data cable protection, 2x2-pole, direct earthing, 12 V

Connectable data cable protection, 2x2-pole, direct earthing, 12 V

Item no. 5080319

Technical data

SPD to EN 61643-11 Type 1+2
SPD to IEC 61643-11 Class I+II
Category Type 1+2 / D1+C2
SPD to IEC 61643-21 Class I+II / D1+C2
Connection cross-section, flexible 0.14 - 1.5 mm²
Connection cross-section, multi-wire 0.14 - 2.5 mm²
Connection cross-section, rigid 0.14 - 2.5 mm²
Version 2x2-pole
Number of poles 4
Insertion loss ≤3 dB
Earthing via: Connection cable / DIN rail
Total discharge current (8/20) 20 kA
Total discharge current (10/350) 2,5 kA
Frequency range 0 - 100 MHz
Cut-off frequency 100 MHz
Maximum continuous voltage AC 12 V
Maximum continuous voltage DC 16 V
Impulse discharge current (10/350) 2.5 kA
Nominal discharge current (8/20 µs) 10 kA
Capacity (wire-wire) ≤30 pF
Capacity (wire-earth) ≤30 pF
Series resistance 1,2 ± 5% ohm
Lightning protection zone LPZ 0→2
Total impulse durability into C2 (8/20) 20 kA
Nominal load current AC 0.425 A
Nominal load current DC 0.6 A
Mounting of input / output Screw terminals
Installation type DIN rail 35 mm
Testing standard IEC 61643-21
Shielding connection available Yes
Shield connection Direct
Protection rating IP20
Protection level wire-wire 130 V
Protection level wire-earth 850 V
Series resistance per wire 1,2 Ω ± 5%
Signalling on device None
Connection system Terminal
Impulse durability wire-wire 10 kV / 5 kA
Impulse durability wire-earth 10 kV / 5 kA
Temperature range -40 - +80 °C

Dimensions

Length 76 mm
Width 13 mm
Height 95 mm
21 V 30 V 4 2x2-pole Terminal 5080321
 
1 piece
Connectable data cable protection, 2x2-pole, direct earthing, 24 V

Connectable data cable protection, 2x2-pole, direct earthing, 24 V

Item no. 5080321

Technical data

SPD to EN 61643-11 Type 1+2
SPD to IEC 61643-11 Class I+II
Category Type 1+2 / D1+C2
SPD to IEC 61643-21 Class I+II / D1+C2
Connection cross-section, flexible 0.14 - 1.5 mm²
Connection cross-section, multi-wire 0.14 - 2.5 mm²
Connection cross-section, rigid 0.14 - 2.5 mm²
Version 2x2-pole
Number of poles 4
Insertion loss ≤3 dB
Earthing via: Connection cable / DIN rail
Total discharge current (8/20) 20 kA
Total discharge current (10/350) 2,5 kA
Frequency range 0 - 100 MHz
Cut-off frequency 100 MHz
Maximum continuous voltage AC 21 V
Maximum continuous voltage DC 30 V
Impulse discharge current (10/350) 2.5 kA
Nominal discharge current (8/20 µs) 10 kA
Capacity (wire-wire) ≤30 pF
Capacity (wire-earth) ≤30 pF
Series resistance 1,2 ± 5% ohm
Lightning protection zone LPZ 0→2
Total impulse durability into C2 (8/20) 20 kA
Nominal load current AC 0.425 A
Nominal load current DC 0.6 A
Mounting of input / output Screw terminals
Installation type DIN rail 35 mm
Testing standard IEC 61643-21
Shielding connection available Yes
Shield connection Direct
Protection rating IP20
Protection level wire-wire 150 V
Protection level wire-earth 850 V
Series resistance per wire 1,2 Ω ± 5%
Signalling on device None
Connection system Terminal
Impulse durability wire-wire 10 kV / 5 kA
Impulse durability wire-earth 10 kV / 5 kA
Temperature range -40 - +80 °C

Dimensions

Length 76 mm
Width 13 mm
Height 95 mm
37 V 52 V 4 2x2-pole Terminal 5080323
 
1 piece
Connectable data cable protection, 2x2-pole, direct earthing, 48 V

Connectable data cable protection, 2x2-pole, direct earthing, 48 V

Item no. 5080323

Technical data

SPD to EN 61643-11 Type 1+2
SPD to IEC 61643-11 Class I+II
Category Type 1+2 / D1+C2
SPD to IEC 61643-21 Class I+II / D1+C2
Connection cross-section, flexible 0.14 - 1.5 mm²
Connection cross-section, multi-wire 0.14 - 2.5 mm²
Connection cross-section, rigid 0.14 - 2.5 mm²
Version 2x2-pole
Number of poles 4
Insertion loss ≤3 dB
Earthing via: Connection cable / DIN rail
Total discharge current (8/20) 20 kA
Total discharge current (10/350) 2,5 kA
Frequency range 0 - 100 MHz
Cut-off frequency 100 MHz
Maximum continuous voltage AC 37 V
Maximum continuous voltage DC 52 V
Impulse discharge current (10/350) 2.5 kA
Nominal discharge current (8/20 µs) 10 kA
Capacity (wire-wire) ≤30 pF
Capacity (wire-earth) ≤30 pF
Series resistance 1,2 ± 5% ohm
Lightning protection zone LPZ 0→2
Total impulse durability into C2 (8/20) 20 kA
Nominal load current AC 0.425 A
Nominal load current DC 0.6 A
Mounting of input / output Screw terminals
Installation type DIN rail 35 mm
Testing standard IEC 61643-21
Shielding connection available Yes
Shield connection Direct
Protection rating IP20
Protection level wire-wire 170 V
Protection level wire-earth 850 V
Series resistance per wire 1,2 Ω ± 5%
Signalling on device None
Connection system Terminal
Impulse durability wire-wire 10 kV / 5 kA
Impulse durability wire-earth 10 kV / 5 kA
Temperature range -40 - +80 °C

Dimensions

Length 76 mm
Width 13 mm
Height 95 mm