V20C3PH600, 5094 60 5, 5094605, V20 surge arrester, Type 2, for PV systems, Photovoltaics surge arrester, chống sét pin mặt trời
This product is no longer in stock
Availability date:
V20C3PH600, 5094 60 5, 5094605, V20 surge arrester, Type 2, for PV systems, Photovoltaics surge arrester, chống sét pin mặt trời
V20C3PH600, 5094 60 5, 5094605, V20 surge arrester, Type 2, for PV systems, Photovoltaics surge arrester, chống sét pin mặt trời
Recipient :
* Required fields
or Cancel
V20C3PH600, 5094 60 5, 5094605, V20 surge arrester, Type 2, for PV systems, Photovoltaics surge arrester, chống sét pin mặt trời
PV type 2 surge protection complete block 600 V and 1,000 V DC
PV surge protection V20, 600 V DC
V20 surge arrester, Type 2, for PV systems
• Complete unit, consisting of plug-in varistor arrester with cut-off unit
• Error-resistant Y circuit for use according to VDE 0100-712 (EN 50539-12)
• For surge protection equipotential bonding to VDE 0100-443 (IEC 60364-4-44)
• Arresting capacity to 40 kA (8/20) per pole
• Low DC protection level: < 2.6 kV (Voc max = 600 V DC)
• Arrester, connectable with thermodynamic cut-off unit and visual function display
• Encapsulated, zinc oxide varistor arrester for use in distributor housings
Application: PV systems with or without separate lightning protection system
V20C3PH600 |
|||
Article number |
5094 60 5 |
||
U max DC |
Uc DC |
V |
600 |
SPD to EN 61643-11 |
Type 2 |
||
Lightning protection zone LPZ |
|
|
1→2 |
Nominal discharge current (8/20) |
In |
kA |
20 |
Maximum discharge current (8/20 μs) |
Imax |
kA |
40 |
Voltage protection level |
Up |
kV |
<2,6 |
Response time |
tA |
ns |
<25 |
Temperature range |
ϑ |
°C |
-40 - +80 |
Protection rating |
|
|
IP20 |
Division unit TE (17.5 mm) |
|
|
3 |
Connection cross-section rigid |
|
|
2.5 - 35 mm² |
Connection cross-section, multi-wire |
|
|
2.5 - 35 mm² |
Connection cross-section, flexible |
|
|
2.5 - 25 mm² |