TYPE 1 AC SURGE PROTECTOR : DS130R

DS130R series Type 1+2 surge protector Pluggable module

 

DS132R-230/G

- Type 1 + 2 AC multipolar surge protector
- In : 20 kA 
- Iimp total : 25 kA
- Pluggable module for each phase
- Remote signaling (option)
- EN 61643-11, IEC 61643-11 compliance

The DS130R is an extreme duty Type 1+2 designed to protect the entrance of the electrical installation.
The DS130R is a one-pole SPD and can be used in common mode or common and differential mode.
DS130R AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+neutral AC networks.
This SPD is DIN rail compatible.

Citel model : DS132R-230/G

Part Number : 571522

Click on the blocks to display detailed characteristics

Electrical characteristics
Hide details
SPD type
follow test IEC 61643-11
  1+2
Network
  230 V single-phase
AC system
  TT-TN
Nominal line voltage
Un
230 Vac
Max. AC operating voltage L-N
Uc
255 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
UT
580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
UT
440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
without disconnection or with safety disconnection
UT
1200 V/300A/200 ms withstand
Operating current
LeakAge current at Uc
Ic
none
Follow current
If
none
Nominal discharge current
15 x 8/20 µs impulses
In
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax
50 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp
12.5 kA
Total lightning current
max. total withstand @ 10/350 µs
Itotal
25 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc
-
Withstand on overvoltages IEEE C62.41.1
  20 kV
Admissible short-circuit current
Isccr
25000 A
Connection mode
  L/N and N/PE
Protection mode(s)
  MC/MD
Protection level
@In (8/20µs) between L/PE
Up L/PE
1.5 kV
Specific energy by pole
max. withstand 10/350 µs
W/R
40 kJ/ohm
Protection level L/PE
Up L/PE
-
Protection level L/N
for multipolar surge protector
Up L/N
1.3 kV
Mechanical characteristics
Hide details
Technology
  MOV
SPD configuration
  Single phase
Connection to Network
  By screw terminals: 2.5-25 mm² / by bus
Format
  Plug-in modular box
Mounting
  Symmetrical rail 35 mm (EN60715)
Housing material
  Thermoplastic UL94-V0
Operating temperature
  -40/+85°C
Protection rating
  IP20
Outdoor application
  N
Failsafe behavior
  Disconnection
Disconnection indicator
  1 mechanical indicator by pole
Spare module
  DSM130R-230 + DSM130R-230/G
Remote signaling of disconnection
  option DS132RS-230/G : output on changeover contac
Associated disconnection devices
Hide details
Thermal disconnector
  internal
Installation ground fault breaker
  Type `S` or delayed
Fuses
  Fuses Type gG - 125 A
Standards compliance
Hide details
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification EAC
 