DS40 series Type 2 surge protector Pluggable - 40 kA
- Type 2 AC Multipolar surge protector
- In : 20 kA
- Imax total : 40 kA
- Pluggable module for each phase
- Remote signaling option
- NF EN 61643-11, CEI 61643-11 compliance
- UL1449 ed.17
Click on the blocks to display detailed characteristics
Electrical characteristics |
Hide details
|
---|
SPD type follow test IEC 61643-11 |
2 | |
Network |
230 V single-phase | |
AC system |
TT-TN | |
Nominal line voltage |
230 Vac | |
Max. AC operating voltage L-N |
385 Vac | |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. without disconnection |
580 Vac withstand | |
Temporary Over Voltage (TOV) Charasteristics - 120 mn without disconnection or with safety disconnection |
440 Vac disconnection | |
Temporary Over Voltage N/PE (TOV HT) without disconnection or with safety disconnection |
1200 V/300A/200 ms withstand | |
Operating current LeakAge current at Uc |
none | |
Follow current |
none | |
Nominal discharge current 15 x 8/20 µs impulses |
20 kA | |
Max. discharge current max. withstand @ 8/20 µs by pole |
40 kA | |
Total Maximal discharge current max. total withstand @ 8/20 µs |
40 kA | |
Admissible short-circuit current |
25000 A | |
Connection mode |
L/N and N/PE | |
Protection mode(s) |
MC/MD | |
Protection level @In (8/20µs) between L/PE |
1.5 kV | |
Residual voltage at 10 kA AC |
1.1 kV | |
Residuel voltage at 5 kA AC |
0.9 kV | |
Protection level L/PE |
- | |
Protection level L/N for multipolar surge protector |
1.8 kV |
Mechanical characteristics |
Hide details
|
---|
Technology |
MOV+GDT | |
SPD configuration |
Single phase | |
Connection to Network |
By screw terminals: 2.5-25 mm² / by bus | |
Format |
Plug-in modular box | |
Mounting |
Symmetrical rail 35 mm (EN60715) | |
Housing material |
Thermoplastic UL94-V0 | |
Operating temperature |
-40/+85°C | |
Protection rating |
IP20 | |
Outdoor application |
N | |
Failsafe behavior |
Disconnection | |
Disconnection indicator |
1 mechanical indicator by pole | |
Spare module |
DSM40-385+DSM40G-600 | |
Remote signaling of disconnection |
option DS42S-385/G : output on changeover contact |
Associated disconnection devices |
Hide details
|
---|
Thermal disconnector |
internal | |
Installation ground fault breaker |
Type `S` or delayed | |
Fuses |
Fuses type gG - 50 A |
Standards compliance |
Hide details
|
---|
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Certification | EAC |