MLPC1-277L-V/50, MLPC1-440LY-R, MLPC2-230L-R, MLPC2-230L-V/ESP, MLPCH1-230L-V, chống sét đèn LED chiếu sáng, chống sét đèn LED

MLPC1-277L-V/50, MLPC1-440LY-R, MLPC2-230L-R, MLPC2-230L-V/ESP, MLPCH1-230L-V, chống sét đèn LED chiếu sáng, chống sét đèn LED

MLPC1-277L-V/50, MLPC1-440LY-R, MLPC2-230L-R, MLPC2-230L-V/ESP, MLPCH1-230L-V, chống sét đèn LED chiếu sáng, chống sét đèn LED

 

MLPC SERIES : MLPC

MLPC series Type 2 (or 3) SPD for LED lighting system Very compact - Plate mounting

 

MLPC1-230L-V

 

- Type 2 (or 3) surge protectors for LED
- Class 1
- Very compact
- Plate mounting
- Screw terminal connection
- Status indicator
- Disconnection AC end of life
- EN 61643-11 compliance

 

The MLPC range is a comprehensive series of AC surge protectors dedicated to LED lighting system. The MLPC are very compact to be integrated into luminaires and are available 2 modes of connection (screw terminal or spring).

Citel model : MLPC1-230L-V

Part Number : 831221

Click on the blocks to display detailed characteristics

Electrical characteristics
Hide details
SPD type
follow test IEC 61643-11
  2/3
Network
  220-240 V single-phase
AC system
  TT/TN
Nominal line voltage
Un
230-277 Vac
Max. AC operating voltage L-N
Uc
320 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
UT
580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
UT
440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
without disconnection or with safety disconnection
UT
1200 V/300A/200 ms disconnection
Residual Current
LeakAge current at Uc
Ipe
none
Nominal discharge current
15 x 8/20 µs impulses
In
5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax
10 kA
Total lightning current
max. total withstand @ 10/350 µs
Itotal
20 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc
10 kV/5 kA
Withstand on overvoltages IEEE C62.41.1
  10 kV/10 kA
Admissible short-circuit current
Isccr
10000 A
Max. load current
IL
5 A
Protection mode(s)
  MC/MD
Protection level
Up
1.5 kV
Protection level CM/DM
@In (8/20µs) and @ 6kV (1.2/50µs)
Up mc/md
1.5 kV/ 1.5 kV
Protection level L/PE
Up L/PE
1.5 kV
Protection level L/N
for multipolar surge protector
Up L/N
1.5 kV
Mechanical characteristics
Hide details
Technology
  MOV+GDT
Connection to Network
  2 screw terminals opposite side in/out - wire 2.5
Mounting
  on plate
Housing material
  Thermoplastic UL94-V0
Operating temperature
  -40/+85°C
Protection rating
  IP20
Failsafe behavior
  Disconnection and AC line cut-off
Disconnection indicator
  Led green OFF and AC network cut-off
Voltage/operating indicator
  Green Led ON
Remote signaling of disconnection
  no
Associated disconnection devices
Hide details
Thermal disconnector
  internal
Installation ground fault breaker
  Type `S` or delayed
Standards compliance
Hide details
Standards compliance EN 61643-11 / IEC 61643-11
Certification EAC / TUV /IMQ
 

RelatedProducts